1st test: PRISME Source, PRS-SI-D1
This test uses a pool of 0.4 m2 of HTP (hydrogenated tetra propylene) in a 120 m3 room, ventilated using a renewal rate of 4.7 h-1 (560 m3/hour). The admission and extraction ducts are located in the upper part of the room.
Download the data files DATA-PRS_SI_D1.zip
Watch the test images
Watch the test videos

DIVA facility before the PRS-SI-D1 test © IRSN

DIVA facility during the PRS-SI-D1 test © IRSN

DIVA facility after the PRS-SI-D1 test © IRSN
2nd test: PRISME Door, PRS-D3
This test uses a pool of 0.4 m2 of HTP (hydrogenated tetra propylene) in a 120 m3 room, connected to an adjacent room via an open door. Each room is ventilated using a renewal rate of 4.7 h-1 (560 m3/hour). The admission and extraction ducts are located in the upper part of the room. Targets, composed of PVC rods, were placed in the adjacent room.
Download the data files PRS_DOOR_D3-database.zip
Watch the test images
Watch the test videos

DIVA facility before the PRS-D3 test © IRSN

DIVA facility during the PRS-D3 test © IRSN

DIVA facility after the PRS-D3 test © IRSN